It would not get that heavy of a load put on it. I was thinking of using it in either short lengths for tying batteries together in a battery bank or for running from a single battery (or battery bank) to a five hundred watt (or one thousand watt) inverter. I do not think there would be anywhere in either application that the aluminum would contact copper but I will keep your advice in mind about the grease and keeping the connections tight. As for the heat shrink tubing I was looking at it a while back on line and I found it in large rolls for pretty cheap.
RE: What is all this Off Grid Stuff anyhow? And why the civil war over it?
You are viewing a single comment's thread from:
What is all this Off Grid Stuff anyhow? And why the civil war over it?
1000 watts at 12 volts would be 84 amps. The aluminum wire size for that is double 0 (2-0), and using the grease is smart around batteries to avoid corrosion of the aluminum.
Downvoting a post can decrease pending rewards and make it less visible. Common reasons:
Submit
Gotcha. Thanks a bunch. It has just been an idea really. I tend to like copper wire but since I already have the aluminum I have been thinking about it.
Downvoting a post can decrease pending rewards and make it less visible. Common reasons:
Submit
Free is good! use it, and save the copper money for something else!
:)